Model |
: PVC-8 |
|
Accuracy |
: ±0.25% |
|
Retransmission |
: Optional |
|
Display |
: 3½ Digits |
|
Relay |
: 4 SPST |
|
Inputs |
: Universal |
|
|
Features |
|
|
Universal input- Accepts Sensor Inputs (Thermocouple or RTD), Current, Voltage, & mV. |
|
High Indication Accuracy: ± 0.25%. |
|
Sensor Error Compensation (offset) and Break Detection. |
|
4 Alarm outputs. |
|
Status Indicators for outputs. |
|
Programmable Delay time for alarm. |
|
25 Program settings for each alarm. |
|
RS-485 Serial Communication (MODBUS). |
|
24 VDC Sensor Supply. |
|
Parameter Security via Programmable Lockouts. |
|
85 to 270 VAC/DC supply voltage (also available 24 VDC models). |
|
Compliance: CE, RoHS |
|
|
Specifications |
|
|
Display |
: 4-digit (7 segment LED) 0.5" high. |
|
Display Messages |
: “Or” - Appears when measurement exceeds
range or open
sensor is detected.
: “rE” - TC reverse. |
|
Display alternating
between: |
: PV & HA-AL No. for high alarm.
PV & LA-AL No. for low alarm. |
|
LED Status
Annunciators |
: Alarm ON ( 4nos) . |
|
|
|
Power |
: 85 to 270 VAC / DC , 50 or 60Hz, 5VA. |
|
Optional |
: 24VDC (Consult Factory). |
|
|
|
Settings |
: V ia three keys on front panel. |
|
|
|
Memory |
: Nonvolatile EEPROM retains all programmable parameters and values. |
|
|
|
Main Sensor Input |
: Universal |
|
Temperature Units |
: C° / F°. |
|
Resolution |
: Temperature: 1 / 0.1.
Signal input: 0.001,
: 0.01, 0.1 & 1 decimal
: Point selectable. |
|
Thermocouple inputs |
: Alarm ON ( 2nos) . |
|
J |
: -200 to 750°C. |
|
T |
: -200 to 1350°C. |
|
S |
: -200 to 400°C. |
|
E |
: 0 to 1750°C. |
|
N |
: 0 to 1750°C. |
|
U |
: -200 to 900°C |
|
K |
: -200 to 1350 C |
|
R |
: 0 to 1750 C |
|
C |
: 0 to 2300 C |
|
B |
: +150 to 1820 C |
|
L |
: -200 to 600 C |
|
W |
: 0 to 2300 C |
|
RTD input ( 2 wire or 3 wire) |
|
PT100 |
: -100 to 850°C. |
|
PT1000 |
: -200 to 300 C. |
|
Signal inputs |
|
|
Voltage |
: 0 to 10 VDC. |
|
Current |
: 0 to 20 mA. |
|
mV(linear) |
: -5 to 56mV |
|
|
|
Indication Accuracy |
: 0.25% of Span ±1 C (After 20min. W armup) |
|
|
|
Control And Alarm Outputs |
|
Relay Output |
: 5A @ 250V AC or 24VDC. |
|
Optional |
: 12VDC output to drive SSR. |
|
|
|
Output |
: 2 nos. |
|
Alarm modes |
: Alarm High, Alarm Low , Band, Fail output &
Fault diagnosis. |
|
Hysteresis |
: Programmable. |
|
Annunciator |
: Programmable. |
|
Reset Action |
: Programmable - automatic or latched. |
|
Standby Mode |
: Programmable - enable or disable. or disable. |
|
|
|
Linear Dc Output |
: Optional |
|
Re-transmission |
: 0/4 to 20 mA or 0 to 5 V or 0 to 10 V. |
|
Update rate |
: 100msec. |
|
|
|
Environmental Conditions |
|
Operating Range |
: 0 to 50°C. |
|
Storage Range |
: -5 to 50°C. |
|
Humidity |
: 85% max. |
|
|
|
Connection |
: Wire clamping screw terminals. |
|
|
|
Weight |
: 342 grams |
|