PRB-0.6 : 0.6” SS Probe Temp Sensor |
|
|
Special Features |
|
The sensors employ precision interchangeable thermistors and RTD which are compatible with all the major building automation systems. |
|
Designed for temperature sensing in an HVAC and light industrial control applications |
|
Precision interchangeability eliminates the necessity for individual circuit calibration. |
|
Available in threaded PVC version with rugged weatherproof electrical box |
|
Data sheets for the standard items appear on the web at www.omicron-sensing.com |
|
Omicron is able to produce custom sensors in small volumeat standard sensor pricing |
|
|
There are several sensor element ranges to choose from, which guarantee compatibility with all popular DDC systems.The sensor elements are precision thermistors or platinum RTDs. Field calibration is not generally required. The probe is epoxy sealed to prevent moisture from migrating into the probe.
Custom probe lengths, wire types and sensor elements are available for large OEM projects. Ask about our plastics & metal manufacturing capabilities for custom housings as well. |
|
Applications |
|
Omicron Sensing Inc manufactures water temperature sensors This document shows the enclosures and temperature vs resistance curves for the standard sensors. |
|
|
Specifications |
|
|
Nominal Resistance |
: R25=10.00k±1% |
|
B Value |
: B Value |
|
Optimal Operating Temperature Range |
: -40 ~ +120°C |
|
Insulated Resistance |
: 500VDC in water, >100M |
|
Breakdown Voltage |